A pump's motor power tells you what the pump is actually doing. Load Controls power sensors read that power in the motor control cabinet and trip the pump within seconds when it runs dry, cavitates, dead-heads or jams, with nothing installed in the pipework or the hazardous area.
Pumping systems account for close to a fifth of the world's electricity use and up to a quarter of the energy in some industrial plants, according to the Hydraulic Institute. Over its life a pump usually costs more to run and maintain than to buy. Many of the expensive failures happen at light load: a pump that loses its prime or runs against a closed inlet draws less power, not more, so a thermal overload never sees it.
Magnetic-drive, canned and other sealless pumps are the most exposed. Their bearings sit inside the pump and are cooled by the liquid itself, so a dry-running sealless pump can overheat in seconds.
On a centrifugal pump, power rises steadily with flow. That linear relationship is why power works where current does not: at light load a motor's current barely changes, because the change shows up in the power factor instead, so a current relay cannot tell a healthy light-flow pump from a dry one. See why we measure power, not amps.
Set the low trip point above the dead-head power level and it protects against both dry running and dead head. Set the high trip point just above the power at maximum flow to catch jams and bearing problems. A start-up timer ignores the motor's inrush and a trip delay ignores brief spikes, so the pump is not stopped by nuisance trips. You do not need to close the inlet valve to find these levels; the display shows the power at normal operation and we can help you set them.
On a drive-fed pump, current and power both change with speed, and standard sensors are confused by the drive's distorted output. Load Controls measures on the drive output with a Universal Power Cell, which uses Hall effect sensing that is not disturbed by the waveform, and pairs it with the PMP-25V control for trip relays.
Further reading: Why measure power, not amps, Chemical processing, Water and wastewater, IIoT and control system integration
Can a power sensor protect a magnetic-drive or canned pump?
Yes. These pumps are the most exposed to dry running because the pumped liquid cools their internal bearings. The PMP-25 sees the drop in power as soon as the liquid is lost and trips the motor before the bearings overheat.
Does it need anything in the pipework?
No. The sensor mounts in the motor control cabinet and measures the motor supply, so there is nothing to fit in the line, no pipe to cut and no device in the hazardous area.
How is dry running different from dead head?
Both lower the motor power, but a dead-headed centrifugal pump still churns the liquid and draws more power than a dry one. Setting the low trip point above the dead-head level covers both.
Can it be used on a pump with a variable frequency drive?
Yes, with the PMP-25V and a Universal Power Cell on the drive output. Tell us the drive, motor power and supply and we will specify the combination.

Tell us the application, motor size and drive type. We will recommend a model and send you a quotation. 12-month warranty and support from our team in France.